Sploit.io - Search

Product: B&R Automation Studio, version: 4

CVE-2025-11043

Severity: Unknown

Description: An Improper Certificate Validation vulnerability in the OPC-UA client and ANSL over TLS client used in Automation Studio versions before 6.5 could allow an unauthenticated attacker on the network to position themselves to intercept and interfere with data exchanges.

CVSS Score: N/A

Priority

B

CISA Data

EPSS Data

  • EPSS: 0.002060000
  • Percentile: 0.106770000
  • Date: 2026-07-09

ExploitDB

No data available.

HackerOne Data

  • Rank: 10113
  • Reports submitted count: 0
  • Unknown: 0
  • None: 0
  • Low: 0
  • Medium: 0
  • High: 0
  • Critical: 0

GitHub PoCs

    Nuclei Templates

    No data available.

    VulnCheck Data

    Affected Products:

    • B&R Industrial Automation GmbH B&R Automation Studio - Versions: 4, 6

    References:

    Risk Assessment

    1. Risk Assessment
    The vulnerability, CVE-2025-11043, is an Improper Certificate Validation flaw within the OPC-UA client and ANSL over TLS client components of B&R Automation Studio versions prior to 6.5. This means the software isn't rigorously verifying the authenticity of TLS certificates during communication. The CVSS v3.1 score of 7.4 (High) and the CVSS v4.0 score of 9.1 (Critical) indicate a significant risk. The vulnerability is network accessible, requiring no user interaction, and affects both confidentiality and integrity. While availability isn’t directly impacted, successful exploitation can lead to data manipulation or interception. The EPSS score of 0.002060000 suggests a relatively low, but not negligible, probability of exploitation in the wild. This vulnerability poses a business risk, particularly for organizations relying heavily on Automation Studio for critical process control and data acquisition, as compromised data can lead to incorrect process control, faulty analytics, or even production disruptions. The attack complexity is rated as High in CVSS v3.1, but Low in CVSS v4.0, suggesting the attacker needs some understanding of TLS and certificate behavior to successfully exploit the flaw.

    2. Potential Attack Scenarios
    A potential attack scenario involves a Man-in-the-Middle (MITM) attack. An attacker positioned on the same network as a system running a vulnerable version of Automation Studio can intercept and decrypt communications between the Automation Studio client and a server. The attacker could achieve this by spoofing the server's certificate, presenting a rogue certificate that the vulnerable client accepts due to the improper validation. The attack process would involve: 1) The attacker intercepts the initial TLS handshake between the Automation Studio client and the server. 2) The attacker presents a malicious certificate, potentially one they’ve generated themselves. 3) The vulnerable Automation Studio client, failing to properly validate the certificate, accepts it as legitimate. 4) Once the connection is established, the attacker can read, modify, and replay data exchanged between the client and the server. Potential outcomes include stealing sensitive process data, manipulating control signals to disrupt production, or altering configuration settings.

    3. Mitigation Recommendations
    The primary mitigation is to upgrade B&R Automation Studio to version 6.5 or later, which includes the fix for this improper certificate validation vulnerability. This ensures proper TLS certificate validation, protecting data exchanges from interception and manipulation. Secondary mitigation steps include: 1) Implement network segmentation to limit the blast radius of a potential compromise, restricting access to Automation Studio systems. 2) Monitor network traffic for suspicious TLS connections, looking for connections using potentially rogue certificates. 3) Review and strengthen TLS configuration, ensuring the use of strong cipher suites. 4) Consider using a trusted Certificate Authority (CA) for all certificates used in the environment. Further details and the latest updates can be found on the B&R Automation website: https://www.br-automation.com/fileadmin/SA25P004-4f45197f.pdf.

    4. Executive Summary
    B&R Automation Studio, a widely used industrial automation software, is vulnerable to a significant security flaw (CVE-2025-11043) that could allow attackers to intercept and potentially manipulate data exchanged between the software and connected devices. This vulnerability stems from an improper validation of TLS certificates, meaning the software may accept a forged certificate, allowing an attacker on the network to eavesdrop on or alter critical process data. The risk is considered high, potentially impacting the confidentiality and integrity of your automation systems. We recommend upgrading to Automation Studio version 6.5 or later as soon as possible to resolve this vulnerability. Failure to address this issue could lead to production disruptions, inaccurate data, and potential control system compromise, ultimately impacting operational efficiency and potentially safety. Prompt action is crucial to protect your critical infrastructure.